Undervoltage release F/UV230L left, 230V

Order code: F/UV230L

EAN:

Using with a miniature circuit breaker: FB2-63 (Standart), FB3-63 (EVO), FB3-125 (EVO).

 

Turn off the miniature circuit breaker when the voltage is reduced up to the set point.

CAD files
Undervoltage release F/UV left, 230V

 

Standard IEC/EN 60947-1
Using with a miniature circuit breaker (Standart, EVO) FB2-63 (Standart)
FB3-63 (EVO), FB3-125 (EVO)
Rated current In, A 6
Rated frequency, f, Hz 50/60
Rated voltage Un, V ~230
Minimum actuation voltage Ue min, V ~170 ± 5%
Commutation wear resistance 8 000 - electric
8 000 - mechanical
Rated voltage of the insulation Ui, V 500
Rated pulse current output voltage Uimp, V 4 000
Protection class IP20
Cross-section of connecting conductors, mm² up to 25
Bolt tensioning torque, Nm 2.0
Connection side on the left side
Operating position any
Altitude above sea level, m 2 000
Operating temperature range, °C -25...+55
Storage temperature range, °C -25...+70