Signaling contact F/ALCs-0101 2NС for FMP32

Order code: F/ALCs0101

EAN:

Functions:

  • Status signaling of the circuit breaker.
  • Possibility to test the operation of synchronizer, as well as contact groups of signal contact.

 

Algorithm of signal contact operation:

  • contact closure - when the circuit breaker is switched on manually;
  • contact opening - in case of emergency disconnection of the circuit breaker.

 

Standard IEC/EN 60947-5-1
Number of contacts 2NC
Rated voltage Un, V 240AC, 415AC, 250DC, 400DC
Rated frequency, f, Hz 50/60
Commutation wear resistance 6 000 - electric
10 000 - mechanical
Conventional thermal current Ith, А 5
Rated current In, AC-15 1.5A at 240V, 1A at 415V
Rated current Ie, DC-13 0.2A at 250V, 0.1A at 400V
Rated voltage of the insulation Ui, V 690
Rated pulse current output voltage Uimp, V 4 000